← Products

MPR SERIES

MPR-2014

Overcurrent protection and monitoring

Combines current protection, temperature protection and reclosing elements.

MPR-2014

Product features

Current and non-electrical protection

Provides overcurrent protection for feeders, transformers and motors, including three-stage phase overcurrent, earth fault, negative sequence, overload and non-electrical protection.

Breaker control and monitoring

Supports breaker opening, closing, position monitoring, event logging and disturbance recording. Includes eight digital inputs and six relay outputs.

Local display and communications

Dot-matrix LCD with Chinese and English menus. Remote communications use RS485 / Modbus RTU.

Product test reports

Where it fits and why

Verify phase and earth-fault overcurrent, non-electrical protection and reclosing requirements against the protection design.

Feeder vs. overcurrent protection

MPR-2013

Feeder protection and control with selectable communications interfaces.

MPR-2014

Focused on phase and earth-fault overcurrent, breaker monitoring and RS485.

√ Included · ● Optional · — Not listed

FunctionMPR-2013MPR-2014
Current inputs84
Voltage inputs41
Digital inputs228
Relay outputs86
Instantaneous / time-delay overcurrent√√
Instantaneous / definite-time earth-fault overcurrent√√
Directional blocking√—
Voltage blocking√—
Inverse-time overcurrent√√
Inverse-time zero-sequence overcurrent√√
Zero-sequence overvoltage alarm√—
Sensitive earth-fault detection√—
Overload√—
Undervoltage disconnection√—
Underfrequency load shedding√√
Auto-reclosing√√
Accelerated protection√—
Charging protection√—
Negative-sequence overcurrent—√
Inverse-time negative-sequence overcurrent—√
Non-electrical protection—√
Thermal protection—√
Synchronism check√—
CANBUS / IEC 60870-5-103√—
RS485 / Modbus RTU√√
RJ45 / IEC 60870-5-103●—
Disturbance recording√—
Setting-group switching√√
Satellite time synchronization√√
Programmable outputs√√

Drawing and panel checks

  • Panel cutout: 82.5 × 159 mm (W × H). Supply: 86–265 V AC / 86–280 V DC. Communications: RS485 / Modbus RTU.
  • Confirm CT secondary current, zero-sequence measurement, breaker interface and relay outputs.